2024年5月4日发(作者:autocad2008安装包)
SITOP power supply
SITOP modular
The technology power supply
for demanding solutions
Brochure
Edition
08/2016
/sitop-modular
The one, two and three-phase SITOP modular power
supply units are the technology power supplies for
demanding solutions. They offer maximum functionality
and reliability for use in complex plants and machines.
The wide-range input allows connection to almost any
electrical power system worldwide and ensures a high
degree of safety even if there are large voltage
fluctuations.
These high-performance power supply units offer out-
standing overload characteristics: Power Boost delivers up
to three-times the rated current for short periods of time in
order to trigger protective equipment, and with 50% Extra
Power, loads with high inrush current can be connected
without any problems. In case of overload, you can choose
between constant current or latching shutdown.
The extremely high degree of efficiency ensures low
energy consumption and minimal heat loss in the control
cabinet.
The compact metal enclosure, which requires no spacing
at either side, also saves space on the DIN rail. To further
increase availability, SITOP modular power supply units
can be combined with buffer, DC UPS, redundancy and
selectivity modules.
◾ Technology power supply units from 5 – 40 A
for demanding applications
◾ Compact, rugged metal housing
◾ No lateral installation clearances required
◾ Power boost for tripping protective devices
◾ Extra power for high inrush currents
◾ Selectable short-circuit response
◾ Symmetrical load distribution can be selected for
parallel operation
◾ Extremely high efficiency up to 94%
◾ Remote On/Off allows energy savings by means of
standby mode
◾ Operating status via 3 LEDs and signaling contact
◾ Wide ambient temperature range from -25 to +70 °C
◾ Comprehensive certifications, such as cULus, ATEX,
ClassI Div2, IECEx, GL and ABS
◾ Can be expanded with buffer, redundancy, selectivity
and DC UPS modules for enhancing availability
High functionality for every application
SITOP modular offers special functions that facilitate
universal use and flexible adaptation to the application:
Protection of overvoltages caused by
consumers
When connecting inductances such as DC
motors or contactors, voltages in excess of the
rated voltage can be created. During this period, the 24 V
power supply units enter the standby mode, after which
they then supply the set voltage again. This ensures that
the application is continuously supplied.
Parallel connection for performance
enhancement
For the parallel connection of 2 or more power
supply units of the same type, each be set to
“soft characteristics”. This ensures a symmetrical load dis-
tribution that prevents one power supply being subjected
to an unevenly high load and thus its service life being
reduced.
In the individual mode the "hard characteristic" (delivery
status) ensures a constant output voltage, regardless of
the output current.
Adjustable overload response
In the constant current mode (delivery status)
the output current is limited to 1.15 times the
rated current. With a larger load, the output
voltage is reduced to just a few volts.
The constant current also permits the dimensioning of the
cables according to this maximum current.
If the 24 V output should become de-energized,
the latching shutdown operating mode is the
correct choice. The power supply shuts down if
overloaded by 1.15 times the rated current.
To restart, a targeted activation of the power supply is
necessary, e.g. by means of the Remote On/Off function.
2
发布者:admin,转转请注明出处:http://www.yc00.com/xitong/1714759379a2510163.html
评论列表(0条)